Part Number |
RTL 320-25W1-31R |
Order No. |
913105 |
IEC Category to IEC 61643-1/11 /EN 61643-11 |
Class 1+Class 2 /Type 1+Type 2 |
Technology |
Spark Gap & MOV |
Nominal Voltage( UN) |
240 /415 Vac |
Max. continuous operating voltage (UC) |
320Vac (L-N), 260Vac (N-PE) |
Nominal discharge current (8/20 µs) (In) |
25kA (L-N), 100kA (N-PE) |
Lightning impulse current (10/350 µs) (limp) |
25kA (L-N), 100kA (N-PE) |
Specific energy(W/R) |
156.25KJ/ohms(L-N), 2500 KJ/ ohms (N-PE) |
Charge |
12.5As (L-N), 50As (N-PE) |
Follow current extinguishing capability (IfI) |
Infinite |
Voltage protection level (UP) |
1.5kV (L-N), 1.5kV (N-PE) |
Voltage protection level for 5kA (UP) |
1.0kV |
Response time (tA) |
≤100ns |
Short-circuit withstand capability(Iscw) |
25kArms |
Temporary over voltage(TOV) (UT) |
480V/ 120 min (L-N), 1200 ms (N-PE) |
Max. overcurrent protection |
≤250A gL/gG |
TOV characteristic |
Withstand (L-N), Failure mode (N-PE) |
Enclosure dimensions(H×W×D) |
90×73×68.5mm |
Method of mounting |
35mm DIN rail |
Cross-sectional area(max.) |
25mm2 stranded/flexible |
Cross-sectional area(min) |
1.5mm2 stranded/flexible |
Enclosure material |
Thermoplastic UL94V-0 |
Operating status/fault indication |
Green/Red |
Remote indication contact |
Changeover contact |
Switching capacity |
Max(125Vac/1A), Min (5V/1mA) |
Cross-sectional area (max.) |
1.5mm2 stranded/flexible |
Operation temperature range (TU) |
-40℃~+85℃ |
Operation altitude |
≤4km |
Degree of protection |
IP20 |
Relative humidity |
≤95%(max 40℃) |