RTL 320-25W1-31R

Product Description

DIN Rail, combined Type 1 & 2 / Class Ⅰ & Ⅱ SPD for use in AC system at boundaries from LPZ0B-1 and higher.

Features:

Reliable thermo disconnect device

No follow current

High discharge capacity

Capable of protecting terminal equipment

Smaller size

Visual and remote status indication

Multifunctional terminal for connecting conductors and busbars

DIN rail installation

Part Number RTL 320-25W1-31R
Order No. 933101
IEC Category to IEC 61643-1/11 /EN 61643-11 Class 1+Class 2 /Type 1+Type 2
Technology Spark Gap & MOV
Nominal Voltage (Un) 240 /415 Vac
Max. continuous operating voltage (Uc) 320Vac (L-N), 260Vac (N-PE)
Nominal discharge current (8/20 µs) (In) 25kA (L-N), 100kA (N-PE)
Lightning impulse current (10/350 µs) (Iimp) 25kA (L-N), 100kA (N-PE)
Specific energy(W/R) 156.25kJ/ohms(L-N), 2500 KJ/ ohms (N-PE)
Charge 12.5As (L-N), 50As (N-PE)
Follow current extinguishing capability (Ifi) Infinite
Voltage protection level (Up) 1.5kV (L-N), 1.5kV (N-PE)
Voltage protection level for 5kA (Up) 1.0kV
Measured limiting Voltage(MLV) 1.5kV (L-N), 1.5kV (N-PE)
Response time (ta) <25ns
Short-circuit withstand capability(Iscw) 25kArms
Temporary over voltage(TOV) (Ut) 480V/120 min (L-N), 1200 ms (N-PE)
Max. overcurrent protection <2500A gL/gG
TOV characteristic Withstand (L-N), Failure mode (N-PE)
Enclosure dimensions(H×W×D) 90×73×68.5mm
Method of mounting 35mm DIN rail
Cross-sectional area(max.) 25mm² stranded/flexible
Cross-sectional area(min) 1.5mm² stranded/flexible
Enclosure material Thermoplastic UL94V-0
Operating status/fault indication Green/Red
Remote indication contact Changeover contact
Switching capacity Max(125Vac/1A), Min (5V/1mA)
Cross-sectional area (max.) 1.5mm² stranded/flexible
Operation temperature range (Tu) -40℃~+85℃
Operation altitude ≤4km
Degree of protection IP20
Relative humidity ≤95%(max 40℃)
Enclosure material CE