Power Supply System Class III Surge Protector
Product introduction
Summary
RL *-M3R is designed as fine protection for electronic devices
- For installation at LPZ 1-2or higher, applied in SPD Class III (Class D) for power supply system
- Designed according to IEC 61643-11
Main character
- Green light indicates normal and red light indicates fault
- Single phase protection
- Remote signaling connector for fault indication
Application
- RL *-M3R provides fine protection for single phase power of low power supply system; e.g. icebox, air conditioner, photocopy, communication equipment, network equipment and so on
Application environment
- Temperature: -40℃…+80℃
- Relative humidity: ≦95% (25°C)
Part Number | RL 12-M3R | RL 24-M3R | RL 48-M3R | RL 60-M3R | RL120-M3R | RL230-M3R |
---|---|---|---|---|---|---|
Order No. | 931001 | 931002 | 931003 | 931004 | 931005 | 931006 |
Nominal a.c voltage (UN) | 12V | 24V | 48V | 60V | 120V | 230V |
Rated voltage (max. continuous a.c voltage)(UC) | 14V | 30V | 60V | 75V | 150V | 320V |
Rated voltage (max. continuous d.c voltage)(UC) | 17V | 30V | 60V | 75V | 150V | 320V |
Nominal load current (IL) | 16A | 16A | 16A | 16A | 16A | 16A |
Nominal discharge current (8/20 µs) (L-N)(In) | 0.7A | 1kA | 1kA | 2.5kA | 2.5kA | 3kA |
Nominal discharge current (8/20 µs) (L+N-PE)(In) | 2kA | 2kA | 2kA | 5kA | 5kA | 5kA |
Combination wave (L-N)(UOC) | 2kV | 2kV | 2kV | 6kV | 6kV | 6kV |
Combination wave (L+N-PE)(UOC) | 4kV | 4kV | 4kV | 10kV | 10kV | 10kV |
Voltage protection level (L-N)(UP) | ≤0.12kV | ≤0.2kV | ≤0.35kV | ≤0.5kV | ≤0.7kV | ≤1.15kV |
Voltage protection level (L/N-PE)(UP) | ≤0.56kV | ≤0.85kV | ≤0.85kV | ≤0.85kV | ≤0.85kV | ≤0.85kV |
Response time(L-N)(TA) | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
Response time(L/N-PE)(TA) | ≤100ns | ≤100ns | ≤100ns | ≤100ns | ≤100ns | ≤100ns |
Max. back up fuse | 16A gL/gG | 16A gL/gG | 16A gL/gG | 16A gL/gG | 16A gL/gG | 16A gL/gG |
Short-circuit withstand capability at max. Buckup fuse | 6kArms | 6kArms | 6kArms | 6kArms | 6kArms | 6kArms |
Operating temperature range(TU) | -40℃…+80℃ | |||||
Cross-sectional area | 0.5mm2~6mm2 solid/4 mm2 flexible | |||||
Mounting on | 35mm DIN rail | |||||
Enclosure material | Purple thermoplastic UL94-V0 | |||||
Dimension | 1.5 mods | |||||
Type of remote signaling contact | Break contact | |||||
Switching capacity a.c | 250V/0.5A | |||||
Switching capacity d.c | 250V/0.1A,125V/0.2A,75V/0.5A | |||||
Cross-sectional area for remote signaling contact | Max. 1.5mm2 solid/flexible | |||||
Test standards | IEC 61643-11 | |||||
Certification | CE (LVD,EMC) |
Installation instruction
According to lightning protection zones concept, for installation at LPZ 0A-2 or higher, this surge protector is usually installed in distribution-box or feeder bus of UPS, protecting devices or equipment downstream. Fuse must be installed at the upsteam of the SPD or the lightning protector to make sure that the protected system has double protection. The value of the fuse used in a SPD system should be
conformed to:
- The value of FUSE should not be larger than the max. withstand capacity of the SPD’s backup fuse value.
- Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.
- Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of SPD.
Installation steps
- Mount the SPD on the 35mm DIN rail.
- Connect conductors, the cross-sectional area of the cable must be larger than 6mm2. The withstand voltage value of the cable is not smaller than AC500V; ensure wiring reliable.
- If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (when normal, 1 and 2 open, 2 and 3 close; when fault, the state is reversed).
- After above, switch on the power supply and turn on the circuit breaker, if the SPD’s window indicate green, this indicates the unit is operating normally.
Regularly inspect the operating status, especially after lightning. Once the fuse or circuit breaker upstream break or the SPD’s window indicates red, electrician should check/replace the SPD Installation diagram: