Description
Integrated ethernet SPD, used for protecting wiring network or similar transmission system, at the boundaries from LPZ 0B -2 and higher.
Features
- High discharge capacity
- Fully shielded design
- Low insertion loss
- Protection for all lines
- Easy to replace
- DIN rail installation
Part Number | RS05J4R |
---|---|
Order No. | 962001 |
Test according to | IEC/EN 61643-21/GB18802.1 |
Number of ports | 2 |
Technology | GDT&TVS |
Nominal Voltage (UN) | 5V |
Max. continuous operating d.c. voltage (UC) | 5V |
Max. continuous operating a.c. voltage (UC) | 3.5V |
Rated load current (45℃) (IL) | 100mA |
C2 nominal discharge current (8/20 µs) per line (In) | 2kA |
Voltage protection level for line-line In C2 (UP) | 13V |
Voltage protection level for line-PE In C2 (UP) | 600V |
Voltage protection level line-line at 1 kV/us C3 (UP) | 40V |
Voltage protection level line-PE at 1 kV/us C3 (UP) | 600V |
Frequency scope for line-line | 0-1000Mbps |
Insertion loss | ≤0.5dB |
Series impedance per line | 3 ohm |
Protection pining | 1/2,3/6,4/5,7/8 |
Enclosure dimensions (H×W×D) | 94×33×27mm |
Connection | RJ45(socket/socket) |
Location category | Indoor only |
Operation temperature range (TU) | -40℃~+80℃ |
Operation altitude | ≤4km |
Degree of protection | IP20 |
Relative humidity | ≤95%(max 40℃) |
Method of mounting | 35mm DIN rail |
Enclosure material | Metal shell |