RS*J4R

Description

Integrated ethernet SPD, used for protecting wiring network or similar transmission system, at the boundaries from LPZ 0B -2 and higher.

Features

  • High discharge capacity
  • Fully shielded design
  • Low insertion loss
  • Protection for all lines
  • Easy to replace
  • DIN rail installation
Part Number RS05J4R
Order No. 962001
Test according to IEC/EN 61643-21/GB18802.1
Number of ports 2
Technology GDT&TVS
Nominal Voltage (UN) 5V
Max. continuous operating d.c. voltage (UC) 5V
Max. continuous operating a.c. voltage (UC) 3.5V
Rated load current (45℃) (IL) 100mA
C2 nominal discharge current (8/20 µs) per line (In) 2kA
Voltage protection level for line-line In C2 (UP) 13V
Voltage protection level for line-PE In C2 (UP) 600V
Voltage protection level line-line at 1 kV/us C3 (UP) 40V
Voltage protection level line-PE at 1 kV/us C3 (UP) 600V
Frequency scope for line-line 0-1000Mbps
Insertion loss ≤0.5dB
Series impedance per line 3 ohm
Protection pining 1/2,3/6,4/5,7/8
Enclosure dimensions (H×W×D) 94×33×27mm
Connection RJ45(socket/socket)
Location category Indoor only
Operation temperature range (TU) -40℃~+80℃
Operation altitude ≤4km
Degree of protection IP20
Relative humidity ≤95%(max 40℃)
Method of mounting 35mm DIN rail
Enclosure material Metal shell